Caldera Paradise Series User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
Spa Control Module
Circuit Breaker
Panel (House)
G.F.C.I.
1
2
3
4
5
TB 1
AB
HOT
ELECTRICAL INSTALLATION
240V WIRING SCHEMATIC DIAGRAM
POWER CONNECTION To connect power to the spa,
refer to “240 VOLT WIRING SCHEMATIC DIAGRAM” and
“POWER CONNECTION ACCESS” illustrations above,
then proceed with the following steps:
1. Remove the screws securing the equipment com-
partment door and remove the door.
2. Remove the screws securing the Control Module wiring
access panel and remove the panel to allow access to the
input power wiring.
NOTE: The 240V wiring diagram is located on the inside of
the Control Module access door.
Inputs from
transformer
Neutral/Ground Bar
Green (Ground)
Red (Hot)
Black (Hot)
White (Neutral)
White (Neutral)
(Panel Neutral)
(Pigtail)
Red
Black
White
GFCI should be located more than
5 ft. and less than 50 ft. from the spa.
Check your local codes.
The Control Module requires a 6 AWG copper, four-wire
electrical service (Line 1, Line 2, Neutral and Ground),
and requires a minimum supply conductor ampacity of
50 amperes. Failure to connect a neutral line will cause
the Control Module to malfunction and will void the
Control Module warranty.
NOTE: The 240V wiring diagram is
located on the back of the Control
Module access panel.
Page 4
240 VOLT INSTALLATION
Your spa contains a Control Module designed to operate at
240V, 60Hz. Installation of a 50 amp. dedicated circuit is
required. The Control Module must be hard wired directly to
a supply circuit that is protected by a Ground Fault Circuit
Interrupter (GFCI).
IMPORTANT NOTE: All electrical connections to the
Control Module must be accomplished by a qualified
electrician in accordance with the National Electrical
Code and in accordance with any local electrical codes
in effect at the time and place of installation.
All electrical connections must be made in accordance with
the wiring information contained in this manual and on the
back of the field wiring access panel of the Control Module.
For all permanently connected units not provided with
integral disconnecting means: The electrical supply for
this product must include a suitable rated switch or cir-
cuit breaker to open all ungrounded supply conductors to
comply with local and national Electrical Codes. The dis-
connecting means must be within sight, and readily
accessible to the user of the spa, but installed at least 5
feet (1.5m) from the spa.
POWER CONNECTION ACCESS
240V WIRING
ACCESS
CONTROL MODULE
WIRING ACCESS PANEL
EQUIPMENT COMPARTMENT
DOOR
CONTROL MODULE
240V
WIRING
ACCESS (2)
OPENINGS ON
RIGHT& LEFT
HAND SIDE
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 23 24

Comments to this Manuals

No comments